The Cube20 BN-PNIO DI8 56006 is a high-performance digital input module engineered for industrial automation control cabinets. Specially designed to operate with a 24V DC voltage (compliant with EN 61131-2 standards), this unit processes I/O signals efficiently while maintaining a compact footprint. It connects seamlessly to sensors, transmitting input signals to main control systems with high speed and absolute precision. Supporting system expansion up to 15 modules, it delivers up to 488 I/O connection points within a narrow 90cm width, helping optimize valuable space inside control cabinets.
Supports expanding up to 15 modules, enabling up to 488 input/output points within a standard 90cm space to maximize performance and installation flexibility.
Built-in short-circuit protection, overload protection, and under-voltage monitoring with diagnostic LEDs for swift status checks and module communication reporting.
| Parameter | Specification Details |
|---|---|
| Technical Data / Header | |
| Material Short Text | Cube20 BN-PNIO DI8 |
| Electrical Data Supply | |
| Norm Operating Voltage | EN 61131-2 |
| Operating Voltage DC | 24 V |
| Operating Voltage Us DC | 24 V |
| Total Current Us Max. | 4 A |
| Total Current UA Max. | 4 A |
| Current Consumption Max. | 150 mA |
| Electrical Data Input | |
| Current Carrying Capacity Max. | 0.7 A |
| Input Filter Time | 1 ms |
| Type Input | PNP (EN 61131-2) |
| Industrial Communication | |
| Supported Protocol | PROFINET |
| Machine Option Management | Yes |
| Bus Data Details | |
| Address Range Inputs Max. | 1,024 Bytes |
| Address Range Outputs Max. | 1,024 Bytes |
| PROFINET Configuration | |
| PROFINET Conformance Class | B |
| PROFINET Addressing | DCP |
| PROFINET Specification | V2.2 |
| Diagnostics & Protection | |
| Short Circuit Diagnosis | Yes |
| Overload Diagnosis | Yes |
| Diagnostic Parameters | Under voltage |
| Diagnostic via Bus | Per module and channel |
| Diagnostic via LED | Per module |
| LED Display | Ethernet connection / data traffic |
| Installation & Mounting | |
| Connection Cross Section Max. | 2.5 mm² / 25 mm² |
| Terminal Row X2 / X3 | Input / Input |
| Mounting Method | Snapped (DIN Rail) |
| Suitable for Mounting Type | (EN 60715), mounting rail |
| Mechanical Details | |
| Dimensions (H × W × D) | 117 mm × 56 mm × 47 mm |
| Environmental Characteristics | |
| Operating Temperature Range | 0°C to 55°C |
| Storage Temperature Range | -20°C to 85°C |