Phoenix Contact PACT RCP-4000A-1A-D140 Current Transformer (Order No.: 2904922) is a modular electrical component specifically designed for AC current measurement. It serves as the core solution for current monitoring in busbar and power line applications, meeting precise current signal acquisition and conversion requirements in power systems, industrial automation, and related fields.
This product features an integrated kit design comprising two primary core components with the following specifications:
| Product type | Current transformer |
| Insulation | double insulation |
| Overvoltage category | III (1000 V, to neutral conductor) |
| IV (600 V, to neutral conductor) | |
| Pollution degree | 2 |
| Conductor structure signal line | 2x 0.22 mm (Signal (tinned)) |
| 1x 0.22 mm (Shielding (tinned)) | |
| Insulation | double insulation |
| Rated insulation voltage | 1000 V AC (rms CAT III) |
| 600 V AC (rms CAT IV) | |
| Test voltage | 10.45 kV DC (60 s) |
| Accuracy class | 0.2 (IEC 61869-10: A1) |
| Designation | Measuring coil |
| Frequency measuring range | 40 Hz ... 20000 Hz |
| Input signal (at 50 Hz) | 100 mV (1000 A) |
| Curve type | Sine |
| Input impedance | 27 kΩ (smallest measuring range) |
| Designation | Measuring coil |
| Output signal (at 50 Hz) | 100 mV (no load, at 1,000 A) |
| Output voltage (in no-load operation) | VOUT = M * dI/dt |
| Output voltage (sinusoidal, in no-load operation) | 100 mV (VOUT = 2 * π * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A)) |
| Connection method | Screw connection |
| Stripping length | 7 mm |
| Screw thread | M3 |
| Conductor cross-section rigid | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section flexible | 0.2 mm² ... 2.5 mm² |
| Conductor cross-section AWG | 24 ... 14 |
| Tightening torque | 0.5 Nm ... 0.6 Nm |
| Operating voltage display | Green LED |
| Item dimensions | |
| Width | 22.5 mm |
| Height | 85 mm |
| Depth | 70.4 mm |
| Measuring coil | |
| Length | 450 mm |
| Diameter | 8.3 mm ±0.2 mm |
| Measuring coil when installed | - |
| Diameter | 140 mm |
| Signal line | |
| Housing material | PC |
| PA | |
| Coil material | Elastollan |
| Measuring coil degree of protection | IP54 (not assessed by UL) |
| Measuring transducer degree of protection | IP20 |
| Ambient temperature (operation) (Measuring coil) | -30 °C ... 80 °C (Measuring coil) |
| Ambient temperature (operation) (Measuring transducer) | -20 °C ... 70 °C (Measuring transducer) |
| Ambient temperature (storage/transport) | -40 °C ... 80 °C (Measuring coil) |
| -25 °C ... 85 °C (Measuring transducer) | |
| Altitude | < 2000 m |
| Permissible humidity (operation) | 5 % ... 95 % (non-condensing) |
| Certificate | CE-compliant |
| Certificate | UKCA-compliant |
| Certificate | CMIM-compliant |
| Identification | UL 61010 Recognized |
| Note | Measuring coil |
| Identification | UL 508 Listed |
| Note | Measuring transducer |
| Electrical isolation | Reinforced insulation in accordance with IEC 61010-1 |
| Standards/regulations | IEC 61010-2-030 |
| IEC 61869-10 | |
Models: Phoenixcontact PACT RCP-4000A-1A-D140 - Current transformer 2904922
| Item number | 2904922 |
| Packing unit | 1 pc |
| Minimum order quantity | 1 pc |
| Weight per piece (including packing) | 312.2 g |
| Weight per piece (excluding packing) | 390.8 g |
| Customs tariff number | 85437090 |
| Country of origin | DE |